Corrosion Control™ System

Multiplexing Sensor Hub

Multiplexing Sensor Hub Hero.psd
Corrosion Control™ System

Multiplexing Sensor Hub

The Multiplexing Sensor Hub™ (MSH) allows station owners to add the Corrosion Control™ Water Separator, Corrosion Detection Sensor, and other sensors to existing sites without having to break concrete to run new conduit and wires. 

Multiplexing Sensor Hub Highlight.psd

DO MORE WITH EXISTING WIRING

The MSH utilizes existing cabling to power and connect up to six total devices to an EVO™ 600 or EVO™ 6000 Automatic Tank Gauge (ATG).


Corrosion Control™ System

The MSH is ideal for use in adding a Corrosion Control Water Separator and Corrosion Detection Sensors to an existing tank sump, providing all necessary input capabilities for this system.

Retrofit Applications

For retrofit applications the MSH can use an existing 4-wire probe or sensor cable to add additional probes or sensors, providing expanded monitoring capabilities without the need to break concrete to run additional cable.

New Installations

For new installations the MSH delivers labor and materials savings by reducing the amount of conduit and cable required for monitoring devices within a containment sump.

MORE CAPABILITIES, LOWER UPGRADE COST

The Multiplexing Sensor Hub™ increases ATG sensor inputs without having to run additional conduit.

General

  • Inputs: (1) LL3 probe, (4) UDP devices, (1) switch/temperature sensor, (1) RS-485 sensor
  • Output to EVO 600/6000 ATG: (1) RS-485

Input Capabilities

Six input channels provide a wide assortment of device communication capabilities:

Channel 1: Always on, for FMP-LL3 digital inventory and leak detection probes.

Channel 2-5: Multiplexed, for 2-wire universal device protocol (UDP) communication devices.

Channel 5: Additional capability for 2-wire devices.

Channel 6: For any dry-contact single pole single throw (SPST) switch, a flow switch, two-wire device, or temperature sensor based on a 10k thermistor.

Theory of Operation

  • The FMP-MSH requires a minimum of four wires connected directly to an EVO 600 with an RS485 module.
    • Power
    • Ground
    • A Communication
    • B Communication
  • The four connections are power, ground, and A and B communication for the RS485 module.
  • If a sump has at two input field cables, conductors from both cables may be used to provide the four conductors required. The A and B conductors must be wired together in a shielded, twisted cable.
  • If it is a new installation, Belden cable #7962A, or equivalent may be used.

Compatibility

The FMP-MSH is capable of supporting the following devices:

Channel 1: FMP-LL3

Channel 2: FMP-DDS-U, FMP-DTS-U, FMP-EIS-U, FMP-DIS-U, FMP-HIS-U, FMP-CDS-U, FMP-LL3-29*

Channel 3: FMP-DDS-U, FMP-DTS-U, FMP-EIS-U, FMP-DIS-U, FMP-HIS-U, FMP-CDS-U, FMP-LL3-29*

Channel 4: FMP-DDS-U, FMP-DTS-U, FMP-EIS-U, FMP-DIS-U, FMP-HIS-U, FMP-CDS-U, FMP-LL3-29*

Channel 5: FMP-DDS-U, FMP-DTS-U, FMP-EIS-U, FMP-DIS-U, FMP-HIS-U, FMP-CDS-U, FMP-LL3-29*, FMP-ULS

Channel 6: FMP-ULS, FMP-UHS, FMP-HFS2, 10K Temperature Sensor

*The FMP-LL3-29 is integrated into the Corrosion Control water separator to detect water level in the vessel.

Multiplexing Sensor Hub

Model Number Description
FMP-MSH Multiplexing Sensor Hub