Sensor Alarm Console
Sensor Alarm Console
The S940 Sensor Alarm Console is a cost effective solution for tank overfill protection and sensor leak detection needs.
STAND-ALONE OVERFILL & LEAK DETECTION
This easy-to-install-and-operate device monitors up to four tanks, containment sumps or interstitial spaces and provides an audible and visual indication of an alarm condition. Two programmable relay outputs are included to sound an external alarm or send a signal to a building control or monitoring system. The weatherproof enclosure allows the sensor alarm console to be conveniently installed indoors or out.
- Simple to install and configure.
- Can be installed indoors or outdoors.
- Cost effective leak detection or overfill solution.
- Connect to remote alarms or external devices.
General
- Input channels: 4 (2-wire float switch sensor inputs)
- Output channels: 2 (dry contact relay outputs)
- Alarm: Internal audible alarm
- LEDs: Alarm, power and output
- Dimensions: 6" x 6" x 4"
- Power requirements: 100-240 VAC +/- 10%, 50/60 Hz, 15 W max
- Operating temperature: -13 to +140 ºF (-25 to +60 ºC)
- Enclosure: NEMA® 4, indoor / outdoor (non-hazardous locations only)
Capabilities
- Tank overfill alarm
- Steel or fiberglass tank interstitial monitoring
- Containment sump monitoring
- General liquid sensor monitoring
- Programmable relay outputs for remote alarm or external device interface
- Compatible with the following sensors:
- TSP-ULS universal liquid sensor
- TSP-HLS high level sensor
- TSP-HFS horizontal float switch
- TSP-UHS universal hydrostatic sensor
Approvals/Certifications
- UL, cUL, associated apparatus, non hazardous location
- Third party certification of leak detection capabilities
Model Number | Description |
---|---|
S940 | Four channel sensor alarm console |
Compatible Sensors
Model Number | Description |
---|---|
TSP-ULS | Universal liquid sump sensor (New orders for use with S940 only) |
TSP-UHS | Universal hydrostatic sensor (for use with S940 only) |
TSP-HLS-30 | High product level sensor, 30" long, installed in tank (EVO™ 550, EVO™ 5000, EVO™ 600, EVO™ 6000 ATGs) |
TSP-HLS-30/SS | High product level sensor, stainless steel 30" long, installed in tanks containing alternative fuels (EVO™ 550, EVO™ 5000, EVO™ 600, EVO™ 6000 ATGs) |
TSP-HLS-15 | High product level sensor, 15" long, installed in tank (EVO™ 550, EVO™ 5000, EVO™ 600, EVO™ 6000 ATGs) |
TSP-HLS-15/SS | High product level sensor, stainless steel 15" long, installed in tanks containing alternative fuels (EVO™ 550, EVO™ 5000, EVO™ 600, EVO™ 6000 ATGs) |
Catalogs
Title | Type | Size | |
---|---|---|---|
FFS-0216 (UL) FFS Product Catalog.pdf | 62.67 MB | ||
FFS-0807 (EN) Product Catalogue.pdf | 48.43 MB | ||
FFS-0367 (UL) Site Starters Ordering Guide.pdf | 52.07 MB |
Manuals
Title | Type | Size | |
---|---|---|---|
000-2147rB_940 RevB S940 Sensor Alarm Console Installation Manual.pdf | 0.76 MB |
Drawings
Title | Type | Size | |
---|---|---|---|
CD_FMS_S940_001.pdf | 0.04 MB | ||
CD_FMS_S940_001.dwg | DWG | 0.27 MB |