Petroleum Control Solutions
Petroleum Control Solutions
For retail fueling and c-store applications, Power Distribution Solutions provide a complete petroleum control, power distribution, and backup power / generator transfer switching solution for an entire location.
- Provides AC power controls required for a typical retail petroleum application.
- Includes emergency stop and service disconnects for dispenser low voltage wiring.
- Optional low voltage circuit disconnects.
- Optional series connected surge suppression for protection of sensitive electronic circuits.
- Individual pump and dispenser contactors allow connection of remote control or monitoring system.
- Pump handle isolation using solid state technology with error detection.
- Marked terminals for easy connection of dispensers, pumps, card readers, fuel management systems and tank monitors.
- Factory assembled and pre-wired, eliminating mounting and wiring of separate components in the field.
AC Power Control Capabilities
- E-stop & reset push buttons
- Emergency stop controls.
- Pump hook isolation.
- Pump status lights.
- Pump contactors.
- Dispenser contactors.
Dispenser Capabilities
- Low voltage disconnect.
- Low voltage protection.
Enclosure Options
- UL Type 1 indoor.
Certifications/Approvals
- UL Listed.
- cUL Listed.
- For compliance with NEC® 514.11 and NFPA® 30A Section 6.7 requirements for Emergency Disconnects at Motor Fuel Dispensing Facilities (controlled by E-Stop system).
- For compliance with NEC® 514.13 requirements for Maintenance Disconnects at Motor Fuel Dispensing Facilities (switches to disconnect individual dispenser circuits for servicing).
General
Dispenser Capacity | 4, 6, 8, 10, & 12 |
Submersible Pump Capacity | 2 - 6 |
Dispenser Data Circuits | 1 Data Pair, 1 Credit Card Pair |
Intercom Circuits | 1 Speaker, 1 Call Button per Dispenser (4 Conductors) 2 Speakers, 2 Call Buttons per Dispenser (8 Conductors) |
Media Circuits | Ethernet Circuits 2-Wire Circuits |
System Components
The Petroleum Control Solutions can be installed with or without integrated low voltage circuit disconnects.
- Petroleum Control Solution
- Petroleum Control Solution with Low Voltage Disconnects
- E-Stop Operator
- Reset Operator
- Pump Run Indicators
- Primary Disconnect
- Secondary Disconnect
Ordering Guide
Complete part numbers have a specific order and are created using the following guidelines:
PCS-XDS YPS-N DGT CB EQR
PCS = Petroleum Control System
XD = # of Dispensers
4 = 4 Dispensers
6 = 6 Dispensers
8 = 8 Dispensers
10 = 10 Dispensers
12 = 12 Dispensers
S = Dispenser Disconnect Switch (optional)
YP = # of Pumps
2 = 2 Pumps
3 = 3 Pumps
4 = 4 Pumps
5 = 5 Pumps
6 = 6 Pumps
S = Pump Dispenser Disconnect Switch (optional)
N DGT CB EQR = Low Voltage Circuit Disconnects
N = No Low Voltage Disconnect Options
or
DGT CB EQR = Low Voltage Disconnect Options
D or G or T = Dispenser Data (choose one)
D = Twisted Pair (No data surge protection)
G = Twisted Pair with data surge protection for current loop
T = Ethernet
C or B = Intercom Data (choose one)*
C = 4 conductors per dispenser
B = 8 conductors per dispenser
E or Q or R = Media/Network Data (choose one)*
E = Ethernet
Q = 4 conductors per dispenser
R = 8 conductors per dispenser
Examples:
PCS-6DS4P-GB = Petroleum Control Solution, (6) dispensers, (4) pumps, with Twisted Pair (with Data Surge Protection for Current Loop) Low Voltage Dispenser Data Disconnects, with (2) Speakers & (2) Call Buttons per Dispenser.
PCS-12D6P-TBE = Petroleum Control Solution, (12) dispensers, (6) pumps, with Ethernet Low Voltage Dispenser Data Disconnects, with (2) Speakers & (2) Call Buttons per Dispenser, with Ethernet Media/Network Data circuit.
PCS-6D4PS-N = Petroleum Control Solution, (6) dispensers, (4) pumps, Pump Disconnect Switch, No Low Voltage Disconnects.
*Dispenser Data Disconnect must be selected for secondary Disconnect Options (e.g. D,G,W, or T)
Featured
Brochures
Title | Type | Size | |
---|---|---|---|
FFS-0829 Configured Controls Datasheet.pdf | 2.55 MB |
Catalogs
Title | Type | Size | |
---|---|---|---|
FFS-0834 Power Integrity Integrated Electrical Controls Catalog.pdf | 47.96 MB |
Manuals
Title | Type | Size | |
---|---|---|---|
44-1070 PCS Installation Guide Rev A 10-31-19.pdf | 4.71 MB | ||
44-1102 PCS+LV Installation Guide Rev A 10-31-19.pdf | 8.2 MB |